Regulatory review: 6 October 2026. This guide covers refrigeration, air conditioning and heat pumps in the EU under Regulation (EU) 2024/573, including relevant temporary derogations.
There is no general rule that all older refrigerants must be reclaimed or recycled after 2025. The answer depends on the equipment, refrigerant GWP, date and activity. Servicing existing equipment and placing equipment on the market have different restrictions. GWP means 100-year global warming potential; the values and mixture calculations used here follow the Regulation.
Servicing existing equipment: Article 13
| Equipment | From | What is prohibited | Exceptions and conditions | Legal provision |
|---|---|---|---|---|
| Refrigeration equipment, regardless of charge size | 1 Jan 2025 | Use of F-gases with GWP ≥ 2500 for maintenance or servicing | Qualifying reclaimed or recycled Annex I gases may be used in existing equipment through 31 Dec 2029. Exceptions: military equipment; applications cooling products below −50 °C; equipment exempted under Article 11(5). | Article 13(3) |
| Air conditioning and heat pumps | 1 Jan 2026 | Use of Annex I F-gases with GWP ≥ 2500 for maintenance or servicing | Qualifying reclaimed or recycled gases may be used in existing equipment through 31 Dec 2031. Article 13(4) does not provide the general military or below −50 °C exceptions found in Article 13(3). | Article 13(4) |
| Stationary refrigeration, excluding chillers | 1 Jan 2032 | Use of Annex I F-gases with GWP ≥ 750 for maintenance or servicing | Qualifying reclaimed or recycled gases: no expiry date specified in this paragraph. Exceptions: military equipment; applications cooling products below −50 °C; cooling nuclear power stations. The earlier GWP ≥ 2500 restriction still applies. | Article 13(5) and 13(3) |
Recovered, recycled and reclaimed are different categories. Recovery means collecting refrigerant; recycling involves basic cleaning; reclamation reprocesses it to performance equivalent to virgin material for the intended use. Recovery alone does not qualify a gas for these exemptions. Reclaimed gas requires the prescribed labelling. Recycled gas must come from the relevant equipment category and may be used only by the undertaking that recovered it during servicing or the undertaking for which that recovery was carried out. See Articles 3, 12(7) and 13(3)–(5).
The 2032 reclaimed/recycled exception does not reopen ordinary refrigeration servicing to gases with GWP ≥ 2500 after the Article 13(3) transition ends. For non-exempt equipment, it concerns the range 750 ≤ GWP < 2500. Excluding chillers from the 750 rule does not exempt them from the earlier 2500 rule. Any shortage derogation under Article 13(6) requires a specific Commission implementing act; it is not automatic.
Equipment placed on the market: refrigeration and chillers
The following tables concern placing on the EU market under Article 11 and Annex IV, not a general deadline for switching off existing systems. Equipment classification and rated capacity must follow the manufacturer's documentation. A self-contained system has no gas-containing parts connected on site.
| Equipment | From | What is prohibited | Exceptions and conditions | Legal provision |
|---|---|---|---|---|
| Domestic refrigerators and freezers | 1 Jan 2015 | HFCs with GWP ≥ 150 | No specific exception in this point. | Annex IV, 2(a) |
| Domestic refrigerators and freezers | 1 Jan 2026 | All F-gases | Site safety exception*. | Annex IV, 2(b) |
| Commercial self-contained refrigerators and freezers | 1 Jan 2022 / 1 Jan 2025 | HFCs with GWP ≥ 150 from 2022; other F-gases with GWP ≥ 150 from 2025 | No specific exception in these points. | Annex IV, 3(b), 3(c) |
| Any self-contained refrigeration equipment, excluding chillers | 1 Jan 2025 | F-gases with GWP ≥ 150 | Site safety exception*; specific temporary derogations below. | Annex IV, 4 |
| Other refrigeration equipment, excluding chillers and categories 4 and 6 | 1 Jan 2025 | F-gases with GWP ≥ 2500 | Applications cooling products below −50 °C. | Annex IV, 5(b) |
| Same category: other refrigeration equipment | 1 Jan 2030 | F-gases with GWP ≥ 150 | Site safety exception*. No separate below −50 °C exception in this point. | Annex IV, 5(c) |
| Commercial multipack centralised refrigeration systems, rated capacity ≥ 40 kW | 1 Jan 2022 | Annex I F-gases with GWP ≥ 150 | Cascade systems: the primary refrigerant circuit may use F-gases with GWP < 1500. | Annex IV, 6 |
| Stationary chillers | 1 Jan 2020 | HFCs with GWP ≥ 2500 | Applications cooling products below −50 °C. | Annex IV, 7(a) |
| Stationary chillers ≤ 12 kW | 1 Jan 2027 | F-gases with GWP ≥ 150 | Site safety exception*; specific temporary derogations below. | Annex IV, 7(b) |
| Stationary chillers ≤ 12 kW | 1 Jan 2032 | All F-gases | Site safety exception*. | Annex IV, 7(c) |
| Stationary chillers > 12 kW | 1 Jan 2027 | F-gases with GWP ≥ 750 | Site safety exception*; semiconductor derogation below. | Annex IV, 7(d) |
Equipment placed on the market: air conditioning and heat pumps
| Equipment | From | What is prohibited | Exceptions and conditions | Legal provision |
|---|---|---|---|---|
| Movable plug-in room air conditioners | 1 Jan 2020 | HFCs with GWP ≥ 150 | No specific exception in this point. | Annex IV, 8(a) |
| Self-contained AC and heat pumps ≤ 12 kW, excluding chillers | 1 Jan 2027 | F-gases with GWP ≥ 150 | Site safety exception*: GWP limit 750 where the clause's conditions are met. | Annex IV, 8(b) |
| Same category: self-contained equipment ≤ 12 kW | 1 Jan 2032 | All F-gases | Site safety exception*: GWP limit 750 where the clause's conditions are met. | Annex IV, 8(c) |
| Monoblock and other self-contained AC and heat pumps > 12 to ≤ 50 kW, excluding chillers | 1 Jan 2027 | F-gases with GWP ≥ 150 | Site safety exception*: GWP limit 750 where the clause's conditions are met. | Annex IV, 8(d) |
| Other self-contained AC and heat pumps under point 8(e), excluding chillers | 1 Jan 2030 | F-gases with GWP ≥ 150 | Site safety exception*: GWP limit 750 where the clause's conditions are met. | Annex IV, 8(e) |
| Single-split systems with a charge below 3 kg | 1 Jan 2025 | Annex I F-gases with GWP ≥ 750 | No specific exception in this point. | Annex IV, 9(a) |
| Air-to-water split systems ≤ 12 kW | 1 Jan 2027 | F-gases with GWP ≥ 150 | Site safety exception*. | Annex IV, 9(b) |
| Air-to-air split systems ≤ 12 kW | 1 Jan 2029 | F-gases with GWP ≥ 150 | Site safety exception*. | Annex IV, 9(c) |
| Split systems ≤ 12 kW | 1 Jan 2035 | All F-gases | Site safety exception*. | Annex IV, 9(d) |
| Split systems > 12 kW | 1 Jan 2029 | F-gases with GWP ≥ 750 | Site safety exception*. | Annex IV, 9(e) |
| Split systems > 12 kW | 1 Jan 2033 | F-gases with GWP ≥ 150 | Site safety exception*. | Annex IV, 9(f) |
*Site safety exception: only where the relevant clause allows it and the safety requirements at the installation site prevent the specified compliant alternative. Cost or customer preference alone is not enough. Points 8(b), 8(d) and 8(e) concern inability to use gases below GWP 150; point 8(c) concerns inability to use alternatives to F-gases. Their fallback GWP limit is 750. Labelling requirements under Article 12(15) also apply. Where several restrictions cover a product, an exception in one point does not cancel another applicable restriction. Stationary dual-duct AC and heat pumps fall under split category 9.
Article 11 also provides a military-equipment exception, a narrowly defined ecodesign exception based on lifecycle CO2-equivalent emissions, and Commission-authorised derogations: Articles 11(1), 11(2) and 11(5). A general claim of energy efficiency does not establish an exemption.
Temporary derogations relevant to specialist equipment
These acts permit only their specified products, refrigerants and periods, with the required labelling. They do not create a general exemption for a whole industry.
- 1 Jan 2025–31 Dec 2028: environmental test chambers for applications below −50 °C, laboratory spray-dryers and freeze-dryers, and laboratory centrifuges; GWP ≥ 150, Annex IV point 4. Implementing Regulation (EU) 2024/2729, Article 1.
- 1 Jan 2025–31 Dec 2028: mechanical cryogenic freezers at −150 °C; GWP ≥ 150, Annex IV point 4. Implementing Regulation (EU) 2024/3120, Article 1.
- 1 Jan 2025–31 Dec 2026: blood transport boxes and blood plasma contact shock freezers; GWP ≥ 150, Annex IV point 4. Implementing Regulation (EU) 2024/3122, Article 1.
- 1 Jan 2027–31 Dec 2029: chillers for semiconductor manufacturing: ≤ 12 kW with GWP ≥ 150; > 12 kW with GWP ≥ 750 only when operating below −50 °C. Annex IV points 7(b) and 7(d); Implementing Regulation (EU) 2026/286, Articles 1–2.
- 1 Jan 2027–31 Dec 2030: specified equipment used in compressed-air refrigerated dryers: stationary chillers ≤ 12 kW and self-contained stationary AC ≤ 12 kW or > 12 to ≤ 50 kW; GWP ≥ 150. Annex IV points 7(b), 8(b) and 8(d); Implementing Regulation (EU) 2026/1975, Articles 1–2.
The separate temporary derogation under Implementing Regulation (EU) 2025/33 expired on 30 June 2026.
Can existing systems and equipment already in stock still be used?
An Annex IV deadline does not automatically require the removal of an existing installation. Servicing must meet Article 13. For equipment lawfully placed on the market before the cutoff, later supply is possible; from one year after that cutoff, evidence of lawful earlier placing on the market is required under Article 11(1).
Commissioning is a separate check. For the categories listed in Article 13(19), the operator needs evidence of the relevant site safety grounds or lawful placing on the market before the deadline. Keep that evidence for at least five years under Article 13(20). Repair parts are allowed under Article 11(1) only without increasing capacity, refrigerant charge or the GWP of the refrigerant used.
What do the rules mean for R404A, R410A and R32?
- R404A, GWP about 3922: above the 2500 servicing threshold; the equipment category and reclaimed/recycled transition dates matter.
- R410A, GWP about 2088, and R134a, GWP 1430: below 2500, so that threshold does not create a blanket servicing ban in 2025 or 2026. New-equipment restrictions and the 2032 stationary-refrigeration rule require separate checks.
- R32, GWP 675: below 750 but above 150. Relevant new split-system deadlines include 2027 for air-to-water and 2029 for air-to-air units ≤ 12 kW, subject to the specified exceptions. A lower GWP does not guarantee unrestricted future use.
Lower GWP does not make a refrigerant a direct replacement or guarantee lower electricity consumption. Check the equipment design, safety requirements and manufacturer-approved options. Read our guide to R32 and air-conditioning energy efficiency. R22 follows separate ozone-depleting-substance rules; see R22, R32 and the options for older systems.
HFC quotas, prices and purchasing
Annex VII sets annual HFC ceilings in tonnes of CO2 equivalent, not tonnes of refrigerant: 42,874,410 for 2025–2026, 21,665,691 for 2027–2029 and 9,132,097 for 2030–2032, before applicable adjustments. These are annual amounts within each period. A declining quota can affect availability, but it does not prove a fixed price increase: demand, stocks and reclaimed supply also matter.
Certification or training requirements depend on the activity and equipment under Article 10. Purchasing covered gases for regulated installation and servicing work is subject to Article 11(6); a buyer declaration does not replace a required qualification. Non-hermetically sealed pre-charged equipment may be sold to an end user only with evidence that it will be installed by a certified undertaking under Article 11(7).
Before ordering, identify the equipment, refrigerant, charge, intended work and applicable deadline. For purchasing enquiries, use our refrigerant wholesale page and specify the refrigerant grade and intended application.